Technical Guidance Document B: Fire Safety.

TGD B is the Irish government's guidance on meeting Part B (Fire Safety) of the Building Regulations. Volume 1 covers every building other than a dwelling house, including apartments. Volume 2 covers dwelling houses. It sets the fire safety sign provisions checked at fire safety certificate stage.

For signage and wayfinding

What it asks of your signs

  • 01Signs indicating escape routes and exits are required in all buildings within Volume 1, lit by natural, artificial or emergency escape lighting so they stay visible (paragraph 1.9.12).
  • 02Signs are also needed at fixed hose reels and fire alarm call points, on fire doors, and on push bar escape doors, with I.S. EN ISO 7010 as the reference for sign content.
  • 03Fire door signs use the blue mandatory colour from ISO 3864-1 and are fixed between 1.6m and 1.8m above floor level, on both sides except cupboards and service ducts (Appendix B6).
  • 04Each refuge needs a sign showing the floor number, and the stair number where there is more than one stair. A refuge in a lobby or stair also gets a blue Refuge Area - Keep Clear sign.
  • 05Firefighting stairs and lobbies need storey identification signs at every landing, with a shaft identifier (A-1, A-2) where there is more than one firefighting shaft (paragraph 5.5.6.9).
  • 06Shopping centres: no part of a public common area should be more than 25m from an exit or directional exit sign (paragraph 1.7.6).
  • 07Fire safety signs are not required inside individual dwellings, and signs needed only once the building is in use fall outside the Building Regulations.

Editions and when they apply

TGD B Volume 1 was substantially rewritten in 2024, replacing the 2006 TGD B for buildings other than dwelling houses. The Department reprinted it in January 2026 with a list of corrections incorporated, and that reprint is the current edition. It applies to works or material changes of use starting on or after 1 May 2025. The 2006 document can still be used where a planning application, Part 8 notice, fire safety certificate or strategic housing decision was in place on or before 30 April 2025, provided the structure of the external walls is erected by 30 April 2028.

Volume 2, Dwelling Houses, remains the 2017 edition, with a separate supplementary guidance document. Apartments are not dwelling houses: a block of flats is designed to Volume 1, Purpose Group 1(c).

What Volume 1 asks of signage

Paragraph 1.9.12 is the core clause. It makes escape route and exit signs a requirement in every building the document covers and ties their visibility to the lighting design, with emergency escape lighting designed to I.S. 3217. It then lists the other signs the fire safety certificate will look for: hose reels, call points, fire doors (to Diagram 86 and Appendix B), push bar doors (to Annex A of I.S. EN 1125) and refuges. Further information on signs is referred to I.S. EN ISO 7010.

Section 5 adds signs for firefighters. Where a firefighting shaft or a stair for firefighting purposes is provided, each landing in the stair and each firefighting lobby gets a storey identification sign that identifies the floor by number. Additional firefighting facilities start in buildings with compartment floors, such as apartment buildings, where the topmost floor is more than 11m above ground (paragraph 5.5.4).

How it compares with the UK

TGD B does not contain the flat indicator sign provisions of Approved Document B Volume 1 or Technical Booklet E, and it does not give letter heights or mounting heights for storey signs. Ireland also has no equivalent of England's regulation 8 for existing buildings. You can choose to use the ADB floor and flat sign format on an Irish block, but that is a design choice, not a TGD B requirement. Fire door signs are where Ireland is more specific than England: TGD B fixes the mounting band and the blue mandatory colour in the appendix.

Under BCAR, the assigned certifier and the design certifier sign off compliance with Part B, and the fire safety certificate application is where the fire safety strategy, including escape signage, is assessed. Treat that strategy as the minimum sign schedule, then add the operational signs the fire safety risk assessment and Safety, Health and Welfare at Work (General Application) Regulations require.

Editions and history

Earlier editions: TGD B 1991, 1997 and 2006 (the 2006 edition was reprinted in 2020). TGD B 2024 Volume 1 was published in March 2024 and reprinted with corrections in January 2026. Volume 2 for dwelling houses dates from 2017.

Sources checked

A summary in our own words, checked on 16 October 2026. It is not the document itself and not legal advice.